Technical Specifications
Voltage ratings: 240V, 480V, 600Y/347V
Trip units: 15A to 250A
Interrupting capacity: 10kAIC to 100kAIC
One-inch pole spacing (except QR 250A frame)
Suitable for spas, hot tubs, kitchens, bathrooms and various construction applications
Field-installable accessories: shunt trip, auxiliary switch, shunt/aux combinations (side-car mounted or internal pockets)
Complies with UL, CSA, NOM, IEC global standards
Range of product: MiCOM P63x
Device short name: P633
Relay application: Transformer
Protection type: Breaker failure, ANSI 50G/51G: earth fault, ANSI 46: negative sequence/unbalance, Restricted earth fault, ANSI 49RMS: thermal overload protection, ANSI 87T: two-winding transformer differential, ANSI 27: undervoltage, ANSI 59: overvoltage, ANSI 81L: underfrequency, Overfrequency
Number of inputs: 1 analog, 1 voltage, 1 temperature sensor, 40 discrete, 12 current input CT...X/5 A and X/1 A
Number of outputs: 2 analog, 30 discrete
Communication port protocol: Ethernet, DNP3, IEC 61850, IEC 60870-5-103, Modbus RTU
Auxiliary supply: 24...60 V DC, 19…72 V, 60...250 V DC, 48…300 V, 100...230 V AC
Network and machine diagnosis type: Fault recording, Event recording, Disturbance recording 16.4 s
Switchgear diagnosis type: CT/VT supervision
Environmental data: Packaging made with recycled cardboard - No
Engine
Brand: Perkins
Model: 1106A-70TAG2
Prime Power: 175.7 hp
Standby Power: 193.2 hp
Displacement: 7.01 L
Cylinders: 6 Inline
Aspiration: Turbo AAC
Cooling: Water Cooled
Governor Type: Mechanical
Fuel Consumption: 16.4 L/h (50%), 24.7 L/h (75%), 33.4 L/h (100%)
Speed: 1500 rpm
Bore × Stroke: 105 × 135 mm
Compression Ratio: 16:1
Injection: Direct
Electrical System: 24 V DC
Lub-Oil Capacity: 16.5 L
Fuel Tank Capacity: 280 L
Coolant Capacity: 21 L
Exhaust Temperature: 525 °C
Dry Weight: 788 kg
Alternator
Brand: Stamford
Model: UCI274F
Prime Power: 152 kVA
Standby Power: 167 kVA
Frequency: 50 Hz
Efficiency: 92%
Protection: IP23
Insulation: Class H
Power Factor: 0.8
Overload Capacity: 110%
Poles: 4
Bearings: 1
Output Voltage: 400/230 V
Max Speed: 2250 rpm