Technical Specifications
Multi-application coverage with one device
Modular and scalable hardware design
Plug-and-play modules unlocking all functionality
Comprehensive default features including communication
Firmware update support for new functionality
Retrofit adapters for SPACOM replacement
Fully configurable protection relay
12 variants for all basic applications
Withdrawable plug-in unit
Replaceable individual hardware modules
Three supervised arc-sensor inputs
IEC 61850 Edition 2 certified
Power supply: 48–250 V DC / 100–230 V AC
Measuring inputs: 3 phase CT, 1 standard Io, 1 sensitive Io, 4 VT
Digital I/O: 31 DI / 15 DO
Arc flash sensors: 3
Communication: IEC 61850 Ed.1/2, Modbus TCP, DNP3 TCP, EtherNet/IP
Ethernet redundancy: RSTP, PRP
Cybersecurity: IEC 62443-4-2 SL1
Mounting: Withdrawable, flush or rack
Protection degree: IP54 (with frame)
–
High torque at low frequency thanks to efficient sensorless vector control
Integrated certified Safe Torque Off (STO) safety function eliminates need for external components
Supports PROFINET, EtherNet/IP, PROFIBUS, USS/Modbus RTU
Intuitive commissioning via Smart Access Module, BOP-2, IOP-2, or SD card
Fast and simple software parameter assignment
Full integration with TIA Portal diagnostics and library concept for easy reuse
Compact design up to 132 kW
Integrated input reactor and EMC filter
Side-by-side mounting for all frame sizes without derating
Engine:
Brand: Cummins
Model: 6CTA8.3-G2
Country of Origin: USA
Producing Country: USA, UK, India
Prime Power: 211 HP
Standby Power: 234 HP
Displacement: 8.3 L
Cylinders: 6
Aspiration System: Turbocharged with Aftercooler
Cooling System: Water-cooled
Governor Type: Electronic
Fuel Consumption 50%: 20 L/h
Fuel Consumption 75%: 30 L/h
Fuel Consumption 100%: 40 L/h
RPM: 1500
Cylinder Arrangement: Inline
Bore x Stroke: 114x135 mm
Compression Ratio: 17.3:1
Injection: Direct
Electrical System: 24 V DC
Oil Capacity: 23.8 L
Coolant Capacity: 12.3 L
Dry Weight: 769 kg
Torque: 1040 Nm
Alternator:
Brand: Stamford
Model: UCI274G
Producing Country: UK
Prime Power: 186 kVA
Standby Power: 206 kVA
Frequency: 50 Hz
Insulation: H
Protection: IP23
Efficiency: 92%
Overload: 110%
Power Factor: 0.8
Poles: 4
Bearings: 1
Output Voltage: 400/230 V
RPM: 2250
Generator Set:
Prime Power: 180 kVA / 144 kW
Standby Power: 200 kVA / 160 kW
Spécifications techniques
–
–
Protection des lignes avec communication différentielle à deux extrémités
Protection sélective par phase séparée, utilisant capteurs ou transformateurs conventionnels
Configurations standard prêtes à l’emploi pour installation rapide et personnalisation
Module enfichable extractible pour installation et tests rapides
Grand affichage graphique pour diagrammes unifilaires personnalisables, accessible localement ou via HMI navigateur web
Services étendus sur le cycle de vie
Protection : surintensité directionnelle/non directionnelle, défaut à la terre, protection et mesure en tension et fréquence
Communication différentielle via fibre optique ou fil pilote, idéale pour transformateur intra-zone
Localisation rapide avancée des défauts en court-circuit et défauts à la terre (optionnelle)
Support IEC 61850 Editions 1 & 2 : HSR, PRP, messages GOOSE, IEC 61850-9-2 LE
IEEE 1588 V2 pour synchronisation temporelle précise
Protocoles pris en charge : Modbus, DNP3, IEC 60870-5-103
–
–