Technical Specifications
Main function: Typical generator and motor protection functions
Certification: ATEX Category 5, EN 60079-14
Inputs/Outputs:
5 predefined variants
Up to 16 current transformers (CT)
Up to 8 voltage transformers (VT)
7–15 binary inputs
9–20 binary outputs
4 fast measuring transducer inputs (10 V or 20 mA)
Hardware flexibility: Expandable/modular SIPROTEC 5 system; 1/6 expansion modules possible; large, small, or no display
Width of housing: 1/3 × 19” to 2 × 19”
Application:
Protection of generators in unit connection of different power
Protection of power plant units per protection group
Generator-transformer variant: protection of generator and transformer
Complex units: additional SIPROTEC 5 devices such as 7UT8x, 7SJ82/85, 7SA/SD/SL86
Motor and generator protection functions including underexcitation protection
Local availability in Mumbai for quick support and delivery
Key Features & Benefits:
Complete motor protection: short-circuit, overload, earth fault, abnormal conditions
Enhanced monitoring: real-time measurement and fault logging
Flexible application: LV and MV motor protection for industrial and utility setups
User-friendly design: easy SCADA/automation integration
Operational efficiency: reduces downtime, improves energy efficiency, extends motor life
Ideal for industries in Mumbai and India: manufacturing plants, utilities, process industries, heavy machinery
Application:
Protects motors during all starting and running sequences
Thermal algorithm optimized for motor characteristics
Thermal monitoring via plant temperature sensors
Standard Functionality:
14 Locked rotor protection
37/37G Undercurrent protection – phase/earth
46BC Broken conductor detection
46PR Phase-rotation reversal
46UB Phase unbalance
50BCL Break capacity limit
86 Lockout
Optional Functionality (7SR57):
27/27Vx Undervoltage protection
32 Power protection
47 Sequence protection
55 Power factor
59/59Vx Overvoltage protection
81R Frequency protection – “df/dt“
Monitoring Functions:
Primary, secondary, and phase sequence current & voltage
Frequency, power, and energy
Fault data, event, and records
Motor start data log
Communication: IEC 60870-5-103, MODBUS-RTU, DNP3, IEC 61850
Main function:
1 differential protection function (standard or auto transformer) with additional stabilization
Up to 2 restricted ground-fault protection functions
Measuring Points:
5 x 3-phase current measuring points
3 x 1-phase current measuring points
3 x 3-phase voltage measuring points
Expandable to 3 sides
Inputs and Outputs:
2 predefined standard variants with 8 current transformers
7 to 19 binary inputs
7 to 23 binary outputs
Hardware Flexibility:
Expandable I/O structure within the SIPROTEC 5 modular system
Housing Width:
1/3 × 19 inches to 2/1 × 19 inches
Interoperability:
Compatible with SIPROTEC 5 and SIPROTEC 4 line protection devices
Applications:
Transformer protection with overload protection
Backup protection for downstream power systems
Ground-fault protection (REF)
Circuit-breaker failure protection
Power supply: 24–48 V DC
Current inputs: 3 phase CT + 1 residual CT
Digital inputs / outputs: 16 DI / 8 DO
Communication ports: 1× RS485 (rear), 1× USB (front)
Supported protocols: IEC 60870-5-101/103, DNP3, Modbus RTU, DeviceNet, SPAbus
Protection functions: Overcurrent, earth fault, breaker failure, recloser, SOTF, inrush protection, motor protection
Mounting type: Flush mounting (30TE)
Display: LCD 128×64 with single-line diagram
Operating temperature: -40 to +65 °C
Front protection rating: IP54
Application: Transformer protection
Power supply: 48–230 V AC/DC
Measuring inputs: 6 phase CT, residual CT, 4 VT 100/110 V
Digital inputs: 6 DI
Digital outputs: 10 DO
Relay type: Differential current relay
Communication: USB, RJ45, RS485
Arc flash protection: Yes
Front protection degree: IP54