Technical Specifications
Power supply: 24–48 V DC
Measuring inputs: 3 phase CT, 1 standard neutral CT, 1 sensitive neutral CT, 4 VT
Digital I/O: 22 DI / 14 DO
Arc flash sensors: 6
Communication protocols: IEC 61850 Ed.1 & Ed.2, Modbus TCP, DNP3 TCP, EtherNet/IP
Ethernet redundancy: RSTP, PRP
Cybersecurity: IEC 62443-4-2 SL1 compliant
Mounting: Withdrawable, flush or rack
Protection degree: IP54 (with frame)
Operating temperature: -40 to +65 °C
Standards: IEC, UL, Marine certified
Power supply: 48–250 V DC / 100–230 V AC
Measuring inputs: 3 LPCT, 1 CSH neutral current input, 4 LPVT
Digital inputs / outputs: 40 DI / 16 DO
Communication protocols: IEC 61850 Ed.1 & Ed.2, Modbus TCP, DNP3 TCP, EtherNet/IP
Cybersecurity: IEC 62443-4-2 SL1, role-based access, secured communication
Mounting: Withdrawable, flush or rack mounted
Display: LCD 128×64 with single-line diagram
Operating temperature: -40 to +65 °C
Protection degree: IP54 (front with mounting frame)
Power supply: 48…230 V AC/DC
Application: Motor Protection
Current inputs: 3 phase CT + residual CT (ring-lug)
Voltage inputs: 4 VT inputs (100/110 V)
Digital I/O: 6 DI, 14 DO
Communication ports: USB (front), RS485, RJ45, RS232
Communication protocols: IEC 61850 Ed.1 & Ed.2, Modbus TCP/RTU, DNP3, IEC 60870-5-101/103
Protection functions: Overcurrent, thermal overload, earth fault, locked rotor, breaker failure, arc flash protection
Mounting: Flush mounting, 30TE case
Display: LCD 128×128 with single-line diagram & ANSI symbols
Certifications: IEC/EN 60255-26
Operating temperature: -40 to +65 °C