Technical Specifications
Power supply: 24–48 V DC
Current inputs: 6 phase CT + residual CT (ring-lug)
Digital inputs / outputs: 6 DI / 9 DO
Communication ports: RS485, RJ45 (Ethernet), USB (front)
Protocols: IEC 61850 Ed.1/2, Modbus TCP/RTU, DNP3, IEC 60870-5-101/103
Protection functions: Generator differential, overcurrent, earth fault, loss of field, pole slip, over/under voltage & frequency, breaker failure (ANSI)
Mounting: Flush mounting (30TE)
Display: LCD 128×128 with single-line diagram / ANSI symbols
Operating temperature: -40 to +65 °C
Front protection degree: IP54