Technical Specifications
Power Supply: 24–34 V DC
Mounting Case Size: 40TE
Digital Inputs (DI): 24
Analog Inputs: 8 RTD (optional)
Digital Outputs (DO): 20
Communication Ports: 1 CAN, 1 Ethernet TCP/IP, 2 SFP, 1 USB
Protection Functions: Phase overcurrent (50/51), Ground fault (50N/51N), Sensitive earth fault (50G/51G), Motor differential (87M), Thermal overload (49), etc.
Dimensions: 205 x 180 x 280 mm (W x H x D)
Weight: 9.35 kg
Certifications: CE, cUL, UKCA
–
Power supply: 24–34 V DC
Digital inputs: 40 DI
Digital outputs: 32 DO
Measuring inputs: 5 CT, 4 VT
Communication: Ethernet RJ45, SFP, USB, RS485, CAN
Protocols: IEC 61850 Ed2.1, Modbus, DNP3
Cybersecurity: IEC 62443 SL2
Display: 7" color touchscreen (IP54, IK07)
Weight: approx. 8.8 kg
Power supply: 24–48 V DC
Current inputs: 3 phase CT + 1 residual CT
Digital inputs / outputs: 16 DI / 8 DO
Communication ports: 1× RS485 (rear), 1× USB (front)
Supported protocols: IEC 60870-5-101/103, DNP3, Modbus RTU, DeviceNet, SPAbus
Protection functions: Overcurrent, earth fault, breaker failure, recloser, SOTF, inrush protection, motor protection
Mounting type: Flush mounting (30TE)
Display: LCD 128×64 with single-line diagram
Operating temperature: -40 to +65 °C
Front protection rating: IP54
Power supply: 48–250 V DC / 100–230 V AC
Measuring inputs: 3 LPCT phase current inputs, 1 CSH neutral current input, 4 LPVT voltage inputs
Digital inputs / outputs: 22 DI / 14 DO
Arc flash protection: Integrated, up to 6 arc sensors
Communication protocols: IEC 61850 Ed.1 & Ed.2, Modbus TCP, DNP3 TCP, EtherNet/IP
Cybersecurity: IEC 62443-4-2 SL1 compliant
Mounting: Withdrawable, flush or rack mounting
Operating temperature: -40 to +65 °C
Protection degree: IP54 (front with flush mounting frame)