Technical Specifications
–
Main Function: Feeder and overcurrent protection for all voltage levels
Inputs & Outputs:
4 current transformers, 4 voltage transformers
11–59 binary inputs, 9–33 binary outputs
Hardware: Modular design with expandable I/O; available with large, small, or no display
Protection Functions:
Directional/non-directional overcurrent protection
Ground fault detection (3I0>, V0>, transient, harmonic, intermittent)
Capacitor bank protection (overcurrent, overload, unbalance, differential)
Over/undervoltage, frequency, power, and arc protection
Fault locator, automatic reclosing (AREC), CB failure protection
Control & Automation:
Graphical logic editor (CFC), point-on-wave switching, interlocking, synchrocheck
Control of circuit breakers and power transformers
Communication:
Fixed Ethernet (RJ45) for DIGSI 5 and IEC 61850
Up to 4 pluggable modules: IEC 61850-8-1, IEC 60870-5-103/104, DNP3, Modbus TCP, PROFINET IO
PRP/HSR redundancy, IEEE C37.94 optical link
Web access & cybersecurity (RBAC, signed firmware, event logging)
Additional Features:
Phasor Measurement Unit (PMU)
IEEE 1588 time sync
Fault recording (up to 80 s @ 8 kHz)
Conformal coating standard
–
Spécifications Techniques
Fonction principale : Protection de distance pour réseaux MT/HT
Déclenchement : Tripolaire, 19 ms minimum
Entrées/Sorties : 4 CT, 4 VT (option), 11/23 entrées binaires, 9/16 sorties binaires
Boîtier : 1/3 × 19 pouces, écran grand ou petit
Revêtement conforme standard
Fonctions :
Protection de distance à 6 boucles
Protection directionnelle de secours
Méthodes de réactance et d’impédance
Configuration via DIGSI 5
Avantages :
Détection rapide et fiable
Intégration facile avec SIPROTEC 4
Idéal pour installations neuves ou modernisées
–
–